Product Description

Product Description

Dual Power Automatic Transfer Switch

 

1.WGQ1(AX1) -160A/4P automatic transfer switch (ATSE) is set the switches and control logic integrated without additional controller, achieve integration of automatic electro mechanical switch, voltage detection, frequency detection, communication interface, electrical, mechanical interlocking functions, automatic, electric remote emergency manual control.

2.This is the logical control panel from various logical order to manage the machines, operate with the gearbox to achieve, switching spring motor storage, instantaneous release of the acceleration, rapid access to sub-circuit or circuits conversion, it is obvious by the state security confinement, greatly improved the performance of various electrical and mechanical properties.

Rated current (Ith) 20
A
40
A
60
A
80
A
100
A
125
A
160
A
250
A
400
A
630
A
800
A
1000
A
1250
A
1600
A
Rated insulation voltage (Ui) 750V 1000V
Rated concussion withstand voltage (Uimp) 8kV 12kV
Rated working voltage (Ue) AC440V
Rated working current(Ie) AC-31A 20 40 63 80 100 125 160 250 400 630 800 1000 1250 1600
AC-35A 20 40 63 80 100 125 160 250 400 630 800 1000 1000 1600
AC-33A 20 40 63 80 100 125 160 250 400 400 630 800 800 1000
Rated connection capacity 10Ie
Rated breaking capacity 8Ie
Rated limited short circuit current (Is) 50kA 70kA 100kA 120kA
Rated short-time withstand current (Is) 7kA 9kA 13kA 26kA 50kA
Transfer I-II or II-I 0.45s 0.6s 1.2s
Control power voltage DC24V, 48V, 110V    AC220V
Electrical consumption
Rated Start 300W 325W 355W 400W 440W
frequency Normal 55W 62W 74W 90W 98W
Weight(kg) 4 pole 7.0 7.2 7.2 7.2 7.5 7.5 8.8 9.0 16.5 17 32 36 40 43

20A~1600A Installation Dimensions

Specification Total size Switch installation Connection terminal
A A1 B B1 C E G H J K L N O P R S T U V ΦX Y Y1 Z
20A 279 243 106 103 169 145 115 19 229 85 7 76 153 30 14 18 2.5 103 20 6 41 94 3
40A 279 243 106 103 169 145 115 19 229 85 7 76 153 30 14 18 2.5 103 20 6 41 94 3
63A 279 243 106 103 169 145 115 19 229 85 7 76 153 30 14 18 2.5 103 12 6 41 94 3
80A 279 243 106 103 169 145 115 19 229 85 7 76 153 30 14 18 2.5 103 12 6 41 94 3
100A 279 243 106 103 169 145 115 19 229 85 7 76 153 30 14 18 2.5 103 12 6 41 94 3
125A 322 300 135 128 230 189 115 10 284 102 7 91 190 36 20 25 3.5 127 18 9 55 125 4
160A 322 300 135 128 230 189 115 10 284 102 7 91 190 36 20 25 3.5 127 18 9 55 125 4
250A 406 362 163 142 230 189 143 4 343 80/102 7 91 252 36 25 30 3.5 142 15 11 57 125 11
400A 552 433 234 222 230 273 189 14 416 180 9 93 323 50 40 38 5 222 18 13 83 193 19
630A 552 433 250 222 284 273 189 14 416 99/180 9 93 323 65 40 45 6 222 18 13 83 193 19
800A 760 633 328 250 284 350 443 28 613 220 11 87 526 65 60 64 8 250 31 13 109 254 54
1000A 760 633 328 250 363 350 443 28 613 220 11 87 526 120 60 64 8 250 31 13 109 254 54
1250A 760 633 336 250 363 350 443 28 613 220 11 87 526 120 80 68 8 250 21 13 110 254 54
1600A 760 633 336 250 363 350 443 28 613 220 11 87 526 120 80 68 10 250 21 13 110 255 54

Q&A

Q1: What is the primary function of the WGQ1(AX1) Dual Power Transfer Switch?

A1: The primary function is to automatically switch electrical loads between two independent power sources, typically the main utility (Normal) power and an emergency backup source (Emergency/Generator power). It ensures power continuity by quickly transferring the load when the normal source fails or its quality degrades.

Q2: What does the “Dual Power” designation mean for this switch?

A2: “Dual Power” signifies that the switch is designed to manage and switch between two separate electrical inputs. This is the standard configuration for most backup systems, providing redundancy by utilizing one main source and one backup source.

Q3: Is the WGQ1(AX1) an Automatic Transfer Switch (ATS)?

A3: Yes, the WGQ1(AX1) operates as an Automatic Transfer Switch (ATS). It constantly monitors the primary power source and initiates the transfer sequence automatically without human intervention upon detecting a fault, and it transfers back when the primary power is restored.

Q4: How does the WGQ1(AX1) ensure safety during the transfer process?

A4: Safety is ensured through mechanical and electrical interlocking. These systems strictly prevent the two power sources from being connected to the load simultaneously. This eliminates the risk of short circuits, back-feeding, and potential damage to equipment or the utility grid.

Q5: In which environments or applications is the WGQ1(AX1) commonly used?

A5: The WGQ1(AX1) is widely used in applications where downtime is unacceptable, such as:

  • Commercial Office Buildings and High-Rise Residential Areas.

  • Small to Mid-sized Data Centers and Server Rooms.

  • Fire Protection and Emergency Lighting Systems.

  • Industrial Facilities and Telecommunication Stations.

Reviews

There are no reviews yet.

Be the first to review “WGQ1(AX1) -160A/4P Dual Power Transfer Switch”

Your email address will not be published. Required fields are marked *

MAECENAS IACULIS

Vestibulum curae torquent diam diam commodo parturient penatibus nunc dui adipiscing convallis bulum parturient suspendisse parturient a.Parturient in parturient scelerisque nibh lectus quam a natoque adipiscing a vestibulum hendrerit et pharetra fames nunc natoque dui.

ADIPISCING CONVALLIS BULUM

  • Vestibulum penatibus nunc dui adipiscing convallis bulum parturient suspendisse.
  • Abitur parturient praesent lectus quam a natoque adipiscing a vestibulum hendre.
  • Diam parturient dictumst parturient scelerisque nibh lectus.

Scelerisque adipiscing bibendum sem vestibulum et in a a a purus lectus faucibus lobortis tincidunt purus lectus nisl class eros.Condimentum a et ullamcorper dictumst mus et tristique elementum nam inceptos hac parturient scelerisque vestibulum amet elit ut volutpat.